W6/W9 series
Magnetic Hydraulic
Circuit Breakers
Features
• Designed for the international market. UL Recognized, CSA Certified,
and VDE approved.
• Ratings to 50 amps.
• Heavy duty #10-32 stud connections. (W9)
• Optional 10 amp auxiliary switch.
• Optional snap-in mounting. (W6)
• Several delay curve options.
• Trip-free operation.
Agency Approvals
UL: Recognized as Supplementary Protector under UL 1077. File
E69543.
CSA: Certified as a Supplementary Protector. File LR15734.
VDE: Approved to VDE 0642/EN 60 934 (Circuit Breakers for Equipment)
License No. 73782.
Electrical Data
Auxiliary Switch: See Auxiliary Switch Ratings Table 2 for details.
Calibration: Breakers will hold 100% of rated current. Breakers may trip
between 101% and 124% of rated load (149% for 400 Hz.
units and 134% for AC/DC units). Breakers must trip at
125% of rated load and above (150% for 400 Hz. units and
135% for AC/DC units).
Dielectric Strength: 50/60 or 400 Hz., 1500V: DC, 1100V.
Insulation Resistance: 100 Megohms at 500VDC.
Endurance: 10,000 on/off cycles - 6000 at rated load, 4000 at no load.
Units tested at six cycles per minute, 1 second on and 9
seconds off at 25°C ambient.
Approvals and Ratings Table 1
W6 Series
UL/CSA (All Circuit Functions)
Maximum
Voltage
65
277
277
277/480
250
250
250
Frequency
(Hz)
DC
50/60
50/60
50/60
400
400
400
Current
Phase
-
1
1
3Ø-Wye
1
1
3Ø-Wye
Interrupting
Rating
(Amps)
0.2 - 50
0.2 - 20
21 - 50
0.2 - 20
0.2 - 20
21 - 50
0.2 - 20
W9 Series
Maximum
Voltage
65
277
277/480
250
250
UL/CSA (All Circuit Functions)
Frequency
(Hz)
Current
Phase
Interrupting
Rating
(Amps)
DC
50/60
50/60
400
400
-
1
3Ø-Wye
1
3Ø-Wye
0.2 - 50
0.2 - 50
0.2 - 20
0.2 - 50
0.2 - 50
Capacity
(Amps)
2,000
5,000
2,500
5,000
2,500
1,250
2,500
Capacity
(Amps)
2,000
5,000
5,000
2,500
2,500
Approvals and Ratings Table 2
UL/CSA
Switch
Number
A
Voltage
50/60 Hz.
125
Current
(Amps)
10
Terminals
WxTxL
.093 x .020 x .250
(2.36 x .51 x 6.40)
Typical Resistance and Impedance
DC 50/60 Hz.
Current
Resistance
Impedance
(Amps)
(Ohms)
(Ohms)
0.2 90
90
1.0 1.2
1.2
2.0 0.28 0.28
5.0 0.04 0.04
10.0
0.013
0.013
20.0
0.004
0.005
30.0
0.0027
0.004
40.0
0.002
0.002
50.0
0.0015
0.0015
400 Hz.
Impedance
(Ohms)
180
2.0
0.50
0.05
0.025
0.0065
0.004
0.003
0.0025
Tolerance: 0.1 - 4.99 ± 15%; 5 - 9.99 ± 20%; 10 - 15 ± 25%; 16 - 30 ± 50%.
Mechanical/Environmental Data
Operating Temperature: -40°C to +85°C.
Humidity: Meets requirements of Mil-STD-202 method 103.
Shock: Tested per Mil-STD-202, method 213, test condition C
(100g @ 6 ms).
Vibration:Tested per Mil-STD-202, method 201, 10-55 Hz., 0.06" (1.52mm)
total excursion in 2 planes.
Fungus And Moisture Resistance: Special moisture resistant finish
applied to all ferrous parts.
Plastic parts are made of inherently
fungus resistant material.
Marking: W6 units have ON and OFF molded on the rocker of rocker
actuated units (rocker actuated VDE units have international
“1” and “0”). W9 units have ON and OFF molded into the area
at the base of the toggle. International “1” and “0” symbols are
marked on the toggle for both W6 and W9.
Mounting: Panel mounted units are mounted with two #6-32 screws
from the front of the panel. Metric models for use with M3 x
0.5 screws are available. Units with snap-in mounting option
snap through the front of the panel. To maintain published
performance specifications, units should not be mounted
more than 90° from their normal upright position.
Weight: Approximately 2.5 ounces per pole.
W6 Series
Maximum
Voltage
65
250
250
415/240
VDE (Circuit Function X)
Frequency
(Hz)
Current
Phase
Interrupting
Rating
(Amps)
DC
50/60
50/60
50/60
-
1
1
0.2-50
0.2-30
31-50
0.2-30
Capacity
(Amps)
2,000
5,000
2,000
5,000
W9 Series
Maximum
Voltage
65
250
250
415/240
VDE (Circuit Function X)
Frequency
(Hz)
Current
Phase
Interrupting
Rating
(Amps)
DC
50/60
50/60
50/60
-
1
1
0.2-50
0.2-30
31-50
0.2-30
Capacity
(Amps)
2,000
5,000
2,000
5,000
VDE
Switch
Number
V1
V2
V3
Voltage
50/60 Hz.
250
250
250
Current
(Amps)
10
5
0.1
Terminals
WxTxL
.110 x .020 x .280
(2.79 x .51 x 7.11)






W91-X113-15 Datasheet, Funktion
Outline Dimensions
W9 Series
Series Trip Model
.281
(7.14)
1.845
(46.86)
.313
(7.95)
LINE
1.940
(49.28)
LOAD
ON
29°
30°
OFF
#10-32
STUD TERMINATION
.14
2.10 (3.56)
(53.34)
2.50
(64.00)
.74
(18.8)
Series Trip Model
With Common Enclosed Auxiliary Switch
.281
(7.14)
2.46
(62.48)
'A'
STYLE
LINE
1.940
(49.28)
C
NO
NC
LOAD
2.50
(64.00)
Series Trip Model
.375
(9.53)
.750
(19.05)
.375
(9.53)
.750
.750
(19.05)
(19.05)
.750
(19.05)
.398
(10.77)
ON ON
.218
(5.54)
OFF OFF
2.065
(52.45)
ON ON ON ON ON ON ON ON
OFF OFF OFF OFF OFF OFF OFF OFF
1.438
(36.53)
2.50
(63.5)
1 POLE
TAPPED #6-32 X .16 (4.06)
DEEP
M3 X 0.5 OPTIONAL
2 POLE
1.500
(38.10) 2.250
3POLE
(57.15) 3.000
(76.20)
4 POLE
Panel Mounting Cutout Detail
.732
(18.59)
.750
.750
(19.05)
(19.05)
.750
(19.05)
1.450
(36.83)
.385
(9.78)
.907
(23.04)
2.065
(52.45)
Notes:
1. Terminal protrusion
dimensions are referenced
from the back of the
mounting panel.
2. Mounting detail tolerance
±.005 (13) unless noted.
3. Outline drawing tolerance ±
.015 (.38) unless noted.
Dimensions in brackets ( )
are in millimeters.
2X Ø .156
(3.96)
PER POLE
.76
1.52 (19.3)
2.28 (38.6)
3.04 (57.9)
(77.2)
1 POLE
2 POLE
3 POLE
4 POLE
Tyco Electronics
700 Westpark Drive
Peachtree City, GA 30269-1498
Specifications and availability subject to change without notice.
13C9699
Printed in U.S.A.
IH/2-00

6 Page







SeitenGesamt 6 Seiten
PDF Download[ W91-X113-15 Schematic.PDF ]

Link teilen




Besondere Datenblatt

TeilenummerBeschreibungHersteller
W91-X113-10Magnetic Hydraulic Circuit BreakersTyco
Tyco
W91-X113-15Magnetic Hydraulic Circuit BreakersTyco
Tyco

TeilenummerBeschreibungHersteller
CD40175BC

Hex D-Type Flip-Flop / Quad D-Type Flip-Flop.

Fairchild Semiconductor
Fairchild Semiconductor
KTD1146

EPITAXIAL PLANAR NPN TRANSISTOR.

KEC
KEC


www.Datenblatt-PDF.com       |      2020       |      Kontakt     |      Suche