Teilenummer GH10RA
Beschreibung MANUAL FOR CONTROLLER
Hersteller GECO
Logo GECO Logo 




Gesamt 20 Seiten
GH10RA Datasheet, Funktion
MANUAL
FOR CONTROLLER
GH10RA
FOR CONTROLLING CENTRAL
HEATING BOILERS WITH
FEEDING SCREW
Program version: 01
USER MANUAL
We request that users carefully study applicable Instructions before connecting and
starting up any of our products.
Should any doubts arise, please contact our Company between 8 a.m. and 4 p.m.
Attention !!! At the bottom of each page you will find last document’s update date. Please, always use the
most recent version of the Instructions, which is available free of charge and will be mailed to you if ordered.
Free Datasheet http://www.datasheet4u.com/






GH10RA Datasheet, Funktion
GH10RA USER MANUAL
5. QUICK START
PAGE 6
To quickly start the GH10RA Controller, perform the following actions:
1. Connect the device to the 230V AC power system (put the plug in the power outlet).
2. Turn the Controller ON by pressing
. Screen appears:
Press
. Screen appears:
and the Controller starts automatic operation according to the factory settings.
Issue I
JANUARY 2012
Free Datasheet http://www.datasheet4u.com/

6 Page









GH10RA pdf, datenblatt
GH10RA USER MANUAL
PAGE 12
6.7. Boiler Burnout Detection
6.7.1. No Fuel
If during automatic operation the boiler outlet water temperature remains below the F08 setting
for a period of time set in the F09 setting, then the Controller considers the boiler as “burned out” and
enters the AL13 alarm condition.
6.7.2. Sudden Drop of Outlet Water Temperature
If during automatic operation the boiler outlet water temperature drops by 10°C, and during that
dropping period the temperature does not rise by 4°C, then the CH and HUW pumps are switched off, and
the Controller goes into the burnout detection mode.
The Controller waits for the period of time set in the F10 setting, during which it checks whether a rise of
4°C occurs.
If YES, then the burnout detection condition is stopped, and the CH and HUW pumps (if necessary) are
started.
If NOT, this means that the furnace is burned out the Controller enters the AL13 alarm condition.
6.8. Maximum Feeder Temperature Detection
The GH10RA Controller is equipped with an additional option of protecting from temperature rise in
the fuel feeder above the permissible value to prevent backfires into the fuel feeder.
The detection is active only in the automatic boiler operation mode (AUTO, MAINTAIN).
When the measured temperature exceeds the value set in the F14 service setting, the fuel feeder activates
for the period of time set in the F16 service setting to eject the ignited fuel from the feeder. During the F16
period the fan remains stopped.
When the time set in F15 service setting elapses, the Controller restores the maximum feeder temperature
detection process.
When the feeder T > 90°C, then fan is stopped, the fuel feeder is started for a period of 2xF16, and the
display indicates the alarm condition AL11 – “Maximum feeder temperature exceeded”. (section 6.5
page 10).
The Controller remains in the alarm condition until user response.
IF F14=0, THEN FEEDER SENSOR OPERATION IS OFF AND THE FUNCTION
OF FEEDER MAX. TEMPERATURE INCREASE DETECTION IS NOT ACTIVE.
Issue I
JANUARY 2012
Free Datasheet http://www.datasheet4u.com/

12 Page





SeitenGesamt 20 Seiten
PDF Download[ GH10RA Schematic.PDF ]

Link teilen




Besondere Datenblatt

TeilenummerBeschreibungHersteller
GH10RAMANUAL FOR CONTROLLERGECO
GECO

TeilenummerBeschreibungHersteller
CD40175BC

Hex D-Type Flip-Flop / Quad D-Type Flip-Flop.

Fairchild Semiconductor
Fairchild Semiconductor
KTD1146

EPITAXIAL PLANAR NPN TRANSISTOR.

KEC
KEC


www.Datenblatt-PDF.com       |      2020       |      Kontakt     |      Suche