Datenblatt-pdf.com


E5AN-H Schematic ( PDF Datasheet ) - Omron

Teilenummer E5AN-H
Beschreibung Advanced Digital Temperature Controller
Hersteller Omron
Logo Omron Logo 




Gesamt 16 Seiten
E5AN-H Datasheet, Funktion
Advanced Digital Temperature Controller
E5AN-H/E5EN-H
(96 x 96 mm and 48 x 96 mm)
www.DataSheet4U.com
CSM_E5AN-H_E5EN-H_DS_E_3_2
A New High-performance Controller: High Resolution, High Speed, and
High Input Accuracy.
Logic Operations and Preventive Maintenance Function. Plus Infrared
Port on Front Panel.
• High-resolution display with 5 digits/0.01°C display.
• High-speed sampling cycle of 60 ms.
• High Accuracy
Thermocouple/Pt input: ±0.1% of PV
Analog input: ±0.1% FS
• Universal inputs on all models (thermocouple, PT, or analog input)
to handle various sensors with one Controller. Models also
available with Remote SP.
• A PV/SV-status display function can be set to automatically
alternate between displaying the status of the Temperature
Controller (auto/manual, RUN/STOP, and alarms) and the PV or
SV.
• Flexible contact outputs with logic operations (AND, OR, and
delays) set from the Support Software (CX-Thermo Ver. 4.0)
• Preventive maintenance for relays in the Temperature Controller
using a Control Output ON/OFF Counter.
• Model available with position-proportional control
96 × 96 mm
E5AN-H
48 × 96 mm
E5EN-H
Refer to Safety Precautions for E5@N/E5@N-H.
Refer to Operation for E5@N/E5@N-H for operating
procedures.
Main I/O Functions
Remote SP Input
One
Event Inputs
None
• Two
• Four
Universal Sensor Inputs
• Universal thermocouple/
Pt/analog
(current/voltage) inputs.
Indication Accuracy
Thermocouple/Pt input:
±0.1% of PV
Analog input:
±0.1% FS
Sampling Period
60 ms
PF Key
(Programmable
key function)
E5AN-H
E5EN-H
3-level Display
Simultaneously displays set items, such as the
PV, SV, and MV.
5-digit Display with high resolution of 0.01°C
Infrared port
USB
Auxiliary Outputs
• Two
• Three
Computer Support Software
CX-Thermo
Control Output 2
(built-in)
Output Unit
• SSR outputs • Relay output
Voltage output (for driving SSR)
• Current output
• Linear voltage output
• Auto/manual switching
• Temperature Controller
status display
• Simple program
function
• Logic operations
• Control output ON/OFF
count alarm
• PV change rate alarm
Models available with
RS-485, RS-422, or
RS-232C
communications
Control Output 1
(built-in)
Output Unit
• SSR outputs • Relay output
Voltage output (for driving SSR)
• Current output
• Linear voltage output
1






E5AN-H Datasheet, Funktion
E5AN-H/E5EN-H
www.DataSheet4U.com
Input Ranges
Thermocouple/Platinum Resistance Thermometer (Fully Universal Inputs)
Input
type
Platinum resistance
thermometer
Thermocouple
Analog input
Name
Pt100
JPt100
K
J
T
EL
U
N
R
S
B
W
PL
II
4 to
20 m
A
0 to
20 m
A
1 to
5V
0 to
5V
0 to
10 V
2300
1800
1700
2300.0
1800.0
1700.0 1700.0
1600
1500
1400
1300
1300.0
1300.0
1300.0
1200
1100
1000
850.0
900
800
700
600
500.0
500
400
500.0
850.0
850.0
500.0
400.0
400.0 400.0
600.0
400.0 400.0
Usable in the following
ranges by scaling:
19999 to 32400,
1999.9 to 3240.0,
199.99 to 324.00, or
19.999 to 32.400
300
200.00
200.00
200.00
200.00
200
100.0
100.0
100
0
0.0 0.0
0.0
100.0
50.00
20.0 50.00100.0 20.0 50.00
50.00
100.0
200.0
200.0 199.9
199.9
200.0
200.0 199.9
200.0
200.0 199.9 200.0
100.0
0.0 0.0
0.0
Setting
number
0
1
2 24 3
4
5
6 21 7
8 22 9 10 23 11 12 13 14 15 16 17 18 19 20 25 26 27 28 29
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
PL II: According to Platinel II electromotive force charts from BASF (previously
Engelhard)
6

6 Page









E5AN-H pdf, datenblatt
Nomenclature
E5AN-H
Temperature unit
Operation indicators
SUB1
SUB2
SUB3
HA
OUT1 RSP STOP
OUT2 CMW MANU
PV
No.1 display
SV
No.2 display
MV No.3 display
Programmable
Function Key/
Auto/Manual Key
PF
A/M
E5AN-H
Level Key
Ir
Mode Key
Up Key
Down Key
Dimensions
E5AN-H
E5EN-H
E5AN-H/E5EN-H
www.DataSheet4U.com
Operation indicators
Temperature unit
SUB1 SUB2
HA SUB3
Operation indicators
RSP
OUT1 STOP
OUT2 CMW MANU
PV
No.1 display
SV No.2 display
MV No.3 display
Mode Key
Level Key
E5EN-H
PF
A/M
Ir
Up Key
Programmable
Function Key/
Auto/Manual Key
Down Key
Mounted Separately
92+00.8
(Unit: mm)
Group Mounted *
(96 × number of units − 3.5)+01.0
92+00.8
96 × 96
6
112
Waterproof
Packing
(Accessory)
79.2
2
120 min.
91
Group mounting does not
allow waterproofing.
Recommended panel thickness is 1 to
8 mm.
Group mounting is not possible in the
vertical direction. (Maintain the specified
92+00.8
mounting space between Controllers.)
To mount the Controller so that it is
waterproof, insert the waterproof
packing onto the Controller.
When two or more Controllers are
mounted, make sure that the
surrounding temperature does not
exceed the allowable operating
temperature specified in the
specifications.
* Group mounting is not possible if an SSR output is used for
control output 1 or 2 and the E53-C3N or E53-C3DN Output Unit
is used. For these combinations, maintain the following mounting
space between Controllers.
Terminal Cover
Mounting Bracket
(Accessory)
(E53-COV16)
(Accessory)
92+00.8
110 min.
Crimp terminal size: M3.5
92+00.8
120 min.
12

12 Page





SeitenGesamt 16 Seiten
PDF Download[ E5AN-H Schematic.PDF ]

Link teilen




Besondere Datenblatt

TeilenummerBeschreibungHersteller
E5AN-HAdvanced Digital Temperature ControllerOmron
Omron

TeilenummerBeschreibungHersteller
CD40175BC

Hex D-Type Flip-Flop / Quad D-Type Flip-Flop.

Fairchild Semiconductor
Fairchild Semiconductor
KTD1146

EPITAXIAL PLANAR NPN TRANSISTOR.

KEC
KEC


www.Datenblatt-PDF.com       |      2020       |      Kontakt     |      Suche